Description

The Bently Nevada 3300/30 79502-01, also cataloged as the 3300/30 Six-Channel Temperature Monitor, operates as a dedicated hardware component for continuous thermal tracking of machinery bearings and stators within 3300 Machinery Protection System platforms.

Hardware Specifications

ParameterSpecification
Model3300/30 79502-01
BrandBently Nevada
OriginUnited States
Weight0.98 kg
Dimensions50.8 mm x 203.2 mm x 228.6 mm
Operating Temp0 to 65 deg C
Power Consumption6.5 W typical
Input Signal Type3-wire RTD (100 ohm Platinum) or Type E, J, K, T Thermocouples
Channel Density6 independent monitor channels
Output Formats4-20 mA or 1-5 VDC recorder options per channel

Machinery Monitoring and TSI Characteristics

This module processes continuous temperature metrics to track thermal gradients associated with high-velocity rotor dynamics and bearing friction. Specifically, the internal conditioning electronics execute cold junction compensation (CJC) for thermocouple inputs alongside lead wire resistance correction for three-wire RTD links. Subsequently, the digitized telemetry coordinates with adjacent rack modules across the passive backplane. Furthermore, the analog input channels deploy localized noise filtering to enforce cross-talk suppression between tightly packed sensor lines. Consequently, the monitor maintains stable temperature calculations and isolates signal drift, ensuring that sudden thermal expansions or localized bearing spikes trigger individual alarm relays without corrupting adjacent channel baselines.

Frequently Asked Questions

Q: How do you change the base input configuration from an RTD to a specific thermocouple type on the 3300/30?

A: You alter the internal input selection profile using plug-in jumpers on the main circuit board assembly. Subsequently, you must modify the corresponding scaling resistor packs to adjust the measurement range before re-calibrating the loop.

Q: What action does the 79502-01 module perform if an external temperature sensor line experiences an open circuit?

A: The onboard diagnostics immediately detect the loss of loop continuity. Subsequently, the monitor bypasses normal alarm logic execution for that specific channel, drives the individual channel OK LED off, and sets the analog recorder output to its maximum limit to flag a fault status.

Field Installation Guidelines

First, insert the 3300/30 module card into an empty monitor slot within the 3300 chassis frame, tightening the front panel thumbscrews to secure the physical ground pathway to the rack. Subsequently, route all field-side sensor leads through independent, grounded metal conduit to maintain optimal cross-talk suppression. Always decouple the low-voltage sensor cables from any high-voltage plant power distribution lines to prevent electromagnetic induction. Finally, connect the outer signal shields to the single-point instrument earth terminal; this structural termination paths ambient common-mode current loops away from the internal processing core.

Additional information

Weight0.98 kg
Dimensions110 × 210 × 60 mm

0.0 Average Rating Rated (0 Reviews)

Rated
0%
Rated
0%
Rated
0%
Rated
0%
Rated
0%

Be the first to review “Bently Nevada 3300/30 79502-01 Six-Channel Temperature Module”

Your email address will not be published. Required fields are marked *

You have to login to add images.

Recently Viewed Items